중요부하를 갖는 계통연계형 인버터의 고조파주입에 의한 단독운전방지 기법

Translated title of the contribution: Anti-islanding Method by Harmonic Injection for Utility Interactive Inverter with Critical Load

Research output: Contribution to journalArticlepeer-review

Abstract

The utility-interactive inverter with critical loads should supply continuous and stable voltage to critical loads even during the grid fault. The conventional control method which performs current control for grid-connected mode and voltage control for stand-alone mode undergoes the critical load voltage variation during grid fault. The critical load voltage may have large transient when the inverter performs mode transfer after the islanding detection. Recently, the indirect current control method which does not have the transient state during not only islanding detection but also the mode transfer has been proposed. However, since the voltage control is maintained even during the grid-connected mode it is difficult to detect the islanding. This paper proposes an active anti-islanding method suitable for the indirect current control method which does not have NDZ(Non-Detection Zone).
Translated title of the contributionAnti-islanding Method by Harmonic Injection for Utility Interactive Inverter with Critical Load
Original languageKorean
Pages (from-to)315-321
Number of pages7
Journal전력전자학회 논문지
Volume17
Issue number4
DOIs
StatePublished - Aug 2012

Fingerprint

Dive into the research topics of 'Anti-islanding Method by Harmonic Injection for Utility Interactive Inverter with Critical Load'. Together they form a unique fingerprint.