지역난방 이용 공동주택 통합배관시스템의 효용성 검증

Translated title of the contribution: Effectiveness Validation of Combined Piping System for Apartment Using District Heating

Research output: Contribution to journalArticlepeer-review

Abstract

This study validates effectiveness of a combined piping system for an apartment using district heating. The existing district heating system is composed of four pipes (four-pipe system), but the suggested combined piping system is composed only of two pipes (two-pipe system). Thanks to this simplification, the two-pipe system will reduce heat loss of supplied heating energy. Performance of the four-pipe system and the two-pipe system were analyzed using TRNSYS 17 in the aspect that 1) If it can provide sufficient heating energy for space heating and hot water simultaneously, and 2) How much of the heat loss of the hot water supply pipe may be reduced. Measured energy consumption were compared with simulation results, that revealed good agreement. This study also proposes an optimal operation strategy of the hot water set temperature for the two-pipe system. It is confirmed that the two-pipe system can provide sufficient heating energy and uses less energy compared to the four-pipe system.
Translated title of the contributionEffectiveness Validation of Combined Piping System for Apartment Using District Heating
Original languageKorean
Pages (from-to)451-461
Number of pages11
Journal설비공학 논문집
Volume30
Issue number10
DOIs
StatePublished - Oct 2018