컴팩트형 VAV 공조기의 성능평가와 경제성 분석에 관한 연구

Translated title of the contribution: A Study on Economic Analysis and Performance Appraisal of Compact Type Variable Air Volume

Research output: Contribution to journalArticlepeer-review

Abstract

Ceiling cooling and heating system that consider load arrangement and space in the ceiling needs to be developed. Therefore, experimental and economic changes were done to verify the performance of compact type VAV. The test results were as follow. 1) Noise test result, measuring approximately 50.4 dB~56.6 dB (before ceiling in landfill), had a better ceiling deadline than the current measure, about a 10 dB noise reduction, so that the office baseline (40~50 dB) noise was judged to be less than test. 2) For the static pressure test result, taking out an outside hydrostatic 25 mmAq, 24.8 mmAq was measured, respectively, at the point. 3) For the life-cycle cost analysis result, the initial investment cost, maintenance replacement costs, and maintenance costs increased 0.2%, but the energy savings ratio was 19.5% while the whole life cycle savings of 40 years LCC was reduced 11.9%.
Translated title of the contributionA Study on Economic Analysis and Performance Appraisal of Compact Type Variable Air Volume