Abstract
In this study, a fan coil unit with an oval-type heat exchanger has been developed. The performance of the present fan coil unit has been investigated, by comparison with the previous fan coil unit with a circular-type heat exchanger. For the fan coil unit with circular- and oval-type heat exchangers, the heat flux and pressure loss through the heat exchangers were measured at standard operating conditions. In addition, the wind speeds exhausted from the fan coil units were compared, for the same fan motor operation. The experimental results show that the average wind speed of the oval-type heat exchanger is 20 percent higher than that of the circular-type heat exchanger. The heat flux in the oval-type heat exchanger is enhanced by 40% or more, over the circular-type heat exchanger.
| Translated title of the contribution | Performance Test of a Fan Coil with an Oval-Type Heat Exchanger |
|---|---|
| Original language | Korean |
| Pages (from-to) | 67-71 |
| Number of pages | 5 |
| Journal | 설비공학 논문집 |
| Volume | 26 |
| Issue number | 2 |
| DOIs | |
| State | Published - Feb 2014 |