Analysis and control of a single-phase-inverter-zigzag-transformer hybrid neutral-current suppressor in three-phase four-wire systems

Research output: Contribution to journalArticlepeer-review

58 Scopus citations

Abstract

This paper presents analysis and control of a hybrid filter that can suppress neutral harmonic currents in three-phase four-wire systems not only with harmonic voltage-source loads but also with harmonic current-source loads. The filter voltampere rating is significantly reduced compared to the conventional neutral-current-suppressing methods. The rectifier part of the neutral harmonic suppressor has been removed by controlling the dc capacitor voltage. The experimental results on a 50-kVA prototype validate the proposed control approach.

Original languageEnglish
Pages (from-to)2201-2208
Number of pages8
JournalIEEE Transactions on Industrial Electronics
Volume54
Issue number4
DOIs
StatePublished - Aug 2007

Keywords

  • Active filter
  • Neutral current
  • Three-phase four-wire
  • Zero-sequence
  • Zigzag transformer

Fingerprint

Dive into the research topics of 'Analysis and control of a single-phase-inverter-zigzag-transformer hybrid neutral-current suppressor in three-phase four-wire systems'. Together they form a unique fingerprint.

Cite this