Assessment of bioaerosols in the public buildings of Korea

Ki Youn Kim, Jae Beom Park, Gyu Yeob Jang, Chi Nyon Kim, Kyung Jong Lee

Research output: Contribution to journalArticlepeer-review

18 Scopus citations

Abstract

The concentration of airborne bacteria and fungi in public buildings is regulated by law in Korea. Levels are investigated during the moderate seasons, spring (March-May) and autumn (September-November), using a six-stage cascade impactor. Total concentrations of airborne bacteria and fungi range from 290 to 940 cfu·m-3 and 330 to 540 cfu·m-3, respectively. The levels of airborne bacteria and fungi are significantly highest in a kindergarten building and lowest in an elderly welfare facility ( p<0.05). The ratio of respirable to total concentration range from 30 to 40% for airborne bacteria and from 55 to 70% for airborne fungi but there is no significant difference among the public buildings examined ( p>0.05). The mean ratios of indoor and outdoor concentrations of airborne bacteria and fungi are below 1.0 regardless of the fraction of particle size and building type. The indoor concentration of airborne bacteria and fungi do not correlate significantly with indoor temperature and relative humidity ( p>0.05). However, this does have a significant positive correlation with CO2 and the number of people per area of the sampling site ( p<0.05), which implies that the activity of residents has considerable effect on the levels of both airborne bacteria and fungi.

Original languageEnglish
Pages (from-to)465-471
Number of pages7
JournalIndoor and Built Environment
Volume16
Issue number5
DOIs
StatePublished - Oct 2007

Keywords

  • Airborne bacteria
  • Airborne fungi
  • Cascade impactor
  • I/O ratio
  • Korea
  • Public building

Fingerprint

Dive into the research topics of 'Assessment of bioaerosols in the public buildings of Korea'. Together they form a unique fingerprint.

Cite this