Abstract
This paper presents a method of decision on where bus splitting is needed to reduce fault current level of power systems and to satisfy the fault current constraints. The method employs a modified fault current constrained optimal power flow (FCC-OPF) with X variables for the candidate locations of splitting and for decision making on whether to split or not, it adopts soft-discretization by augmenting inversed U-shaped penalty terms. Also, this paper discusses the procedure on the adequate selection of bus splitting locations based on the results of the modified FCC-OPF, to reduce the total number of the actions taken.
Original language | English |
---|---|
Pages (from-to) | 76-85 |
Number of pages | 10 |
Journal | Journal of Electrical Engineering and Technology |
Volume | 11 |
Issue number | 1 |
DOIs | |
State | Published - Jan 2016 |
Keywords
- Bus splitting
- Decision making
- Fault current constraints
- Optimal power flow
- Rerun optimization process