Abstract
The vapor injection technique has been used in the heat pump system to improve heating performance and reliability. Especially, it has mostly been applied to extremely cold regions with high compression ratios. In this study, vapor injection was employed in a two-stage heat pump system. A flash tank and an inverter-driven single rotary compressor were also equipped in the heat pump system. The effect of vapor injection was investigated between a compressor frequency of 15∼90% and an ambient temperature of -10∼12°C. In addition, the coefficient of performance (COP) was evaluated for each part-load condition based on SCOP(Seasonal Coefficient of Performance). As a result, the heating capacity and COP of the injection cycle was 6∼13% and -1.4∼7% higher than those of the non-injection cycle under each part-load condition.
| Original language | English |
|---|---|
| State | Published - 2016 |
| Event | 8th Asian Conference on Refrigeration and Air-Conditioning, ACRA 2016 - Taipei, Taiwan, Province of China Duration: 15 May 2016 → 17 May 2016 |
Conference
| Conference | 8th Asian Conference on Refrigeration and Air-Conditioning, ACRA 2016 |
|---|---|
| Country/Territory | Taiwan, Province of China |
| City | Taipei |
| Period | 15/05/16 → 17/05/16 |
Fingerprint
Dive into the research topics of 'Experimental study of flash tank injection on a heat pump system with a rotary compressor'. Together they form a unique fingerprint.Cite this