Hybrid Control Strategy for DC Microgrid Against False Data Injection Attacks and Sensor Faults Based on Lagrange Extrapolation and Voltage Observer

Seong Bae Jo, Dat Thanh Tran, Hieu Xuan Nguyen, Myungbok Kim, Kyeong Hwa Kim

Research output: Contribution to journalArticlepeer-review

Abstract

In this study, to enhance the system reliability under false data injection (FDI) attacks and DC-link voltage (DCLV) sensor failures, a hybrid control strategy for a DC microgrid (DCMG) based on the Lagrange extrapolation and voltage observer is proposed. Under normal conditions without FDI attacks or DCLV sensor failures, the DCMG system works in a distributed control scheme. To enhance the reliability of the system under the DCLV sensor failure or FDI attack, the DCMG system utilizes a hybrid control strategy that combines distributed control with decentralized control. The hybrid control strategy is achieved by the proposed detection algorithms for FDI attacks and DCLV sensor failures. The detection of FDI attacks is accomplished by comparing the predicted secondary controller output based on the Lagrange extrapolation with the actual one. When a power agent detects an FDI attack, its control mode is switched to decentralized control by using the proposed hybrid control strategy. The DCLV sensor failure detection algorithm to enhance system reliability against DCLV sensor failures is achieved by comparing the estimated DCLV with the measured one from the voltage observer. Upon detecting a DCLV sensor failure, the operation of the power agent is switched to the current control mode to sustain the system operation even under DCLV sensor failures. The proposed detection algorithms are simple, effective, and precise, operating without mutual interference that deteriorates the detection accuracy. Simulation and experiments are carried out under various uncertain test conditions to validate the reliability and effectiveness of the proposed control strategy.

Original languageEnglish
Article number1087
JournalElectronics (Switzerland)
Volume14
Issue number6
DOIs
StatePublished - Mar 2025

Keywords

  • distributed DC microgrid
  • false data injection attack
  • hybrid control strategy
  • Lagrange extrapolation
  • sensor fault

Fingerprint

Dive into the research topics of 'Hybrid Control Strategy for DC Microgrid Against False Data Injection Attacks and Sensor Faults Based on Lagrange Extrapolation and Voltage Observer'. Together they form a unique fingerprint.

Cite this