Improvement of intermittent central heating system of university building

Myo Sun Kim, Youngil Kim, Kwang Seop Chung

Research output: Contribution to journalArticlepeer-review

29 Scopus citations

Abstract

Most universities in Korea use intermittent central heating system which operates according to a preset intermittent schedule that is determined based on outdoor air temperature. This system is popular for university buildings due to its low initial cost and simple operation. But since it is not based on feedback control, the indoor thermal comfort is unsatisfactory. In this research, problem with the current control system is studied by experiment and dynamic simulation. The measurement shows that the indoor temperature rises to an uncomfortable range during heating and falls below comfortable range when heating is off. To solve this situation, an on-off control is implemented and simulated using a dynamic simulation program. Since there is a good agreement between experiment and dynamic simulation results, dynamic simulation is used to predict other results with different conditions of interest. The simulation shows that by implementing on-off control, the indoor space can be maintained within comfortable range, moreover using less energy. By reinforcing insulation to the walls that are exposed to the outdoor environment, heating energy can be saved further.

Original languageEnglish
Pages (from-to)83-89
Number of pages7
JournalEnergy and Buildings
Volume42
Issue number1
DOIs
StatePublished - Jan 2010

Keywords

  • Dynamic simulation
  • Experiment
  • Intermittent central heating
  • On-off control
  • PMV
  • Schedule control
  • Thermal comfort

Fingerprint

Dive into the research topics of 'Improvement of intermittent central heating system of university building'. Together they form a unique fingerprint.

Cite this