Abstract
This paper proposes an indirect current control algorithm for seamless transfer of three-phase utility-interactive voltage source inverters. With the proposed method the inverter is able to provide critical loads with a stable and seamless voltage during the whole transition period including both clearing time and control mode change. The LCL filter design which is suitable for the indirect current control is also proposed to meet the harmonic limits. The proposed control method is validated through simulation and experiment.
| Original language | English |
|---|---|
| Article number | 5942180 |
| Pages (from-to) | 773-781 |
| Number of pages | 9 |
| Journal | IEEE Transactions on Power Electronics |
| Volume | 27 |
| Issue number | 2 |
| DOIs | |
| State | Published - 2012 |
Keywords
- Indirect current control
- LCL filter
- seamless transfer
- three-phase inverter
- utility-interactive inverter
Fingerprint
Dive into the research topics of 'Indirect current control for seamless transfer of three-phase utility interactive inverters'. Together they form a unique fingerprint.Cite this