Method for detecting an open-switch fault in a grid-connected NPC inverter system

Ui Min Choi, Hae Gwang Jeong, Kyo Beum Lee, Frede Blaabjerg

Research output: Contribution to journalArticlepeer-review

244 Scopus citations

Abstract

This paper proposes a fault-detection method for an open-switch fault in the switches of grid-connected neutral-point-clamped inverter systems. The proposed method can not only detect the fault condition but also identify the location of the faulty switch. In the proposed method, which is designed by incorporating a simple switching control in the conventional method, the fault condition is detected on the basis of the radius of the Concordia current pattern, and the location of the faulty switch can be identified. By using the proposed method, it is possible to detect the open-switch fault and identify the faulty switch within two fundamental periods, without using additional sensors or performing complex calculations. Simulations and experiments are carried out to confirm the reliability of the proposed fault-detection method.

Original languageEnglish
Article number6096437
Pages (from-to)2726-2739
Number of pages14
JournalIEEE Transactions on Power Electronics
Volume27
Issue number6
DOIs
StatePublished - 2012

Keywords

  • Fault detection
  • fault diagnosis
  • neutral-point-clamped (NPC) inverter
  • open-circuit fault
  • open-switch fault

Fingerprint

Dive into the research topics of 'Method for detecting an open-switch fault in a grid-connected NPC inverter system'. Together they form a unique fingerprint.

Cite this