Abstract
This paper presents a model of the first CIGRE benchmark HVDC system in PSS/E. The model was composed of three parts which: equation converting, DC line, and the control mode selection. The equation conversion uses different equations to calculate the dc voltage and dc power according to normal and abnormal conditions. The DC line calculates the dc current at both dc transmission lines using the dc voltage derived by the equation conversion. The ABB and AREVA control selections are investigated to determine the control mode selection model. Simulation studies have been carried out in PSCAD as well as PSS/E to confirm the performance. The simulation results of PSS/E are similar to those of PSCAD. PSS/E cannot analyze the valve state or firing level such as the harmonic instability or the firing control of the converter.
| Original language | English |
|---|---|
| Title of host publication | IYCE 2015 - Proceedings |
| Subtitle of host publication | 2015 5th International Youth Conference on Energy |
| Publisher | Institute of Electrical and Electronics Engineers Inc. |
| ISBN (Electronic) | 9781467371728 |
| DOIs | |
| State | Published - 5 Aug 2015 |
| Event | 5th International Youth Conference on Energy, IYCE 2015 - Pisa, Italy Duration: 27 May 2015 → 30 May 2015 |
Publication series
| Name | IYCE 2015 - Proceedings: 2015 5th International Youth Conference on Energy |
|---|
Conference
| Conference | 5th International Youth Conference on Energy, IYCE 2015 |
|---|---|
| Country/Territory | Italy |
| City | Pisa |
| Period | 27/05/15 → 30/05/15 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- CIGRE HVDC benchmark model
- HVDC transmission
- PSS/E
- modeling
Fingerprint
Dive into the research topics of 'Modeling of CIGRE benchmark HVDC system using PSS/E compared with PSCAD'. Together they form a unique fingerprint.Cite this