Skip to main navigation Skip to search Skip to main content

Performance comparison between R410A and R32 multi-heat pumps with a sub-cooler vapor injection in the heating and cooling modes

  • Il Yong Cho
  • , Hyeong Joon Seo
  • , Dongwoo Kim
  • , Yongchan Kim
  • Korea University
  • Samsung

Research output: Contribution to journal › Article › peer-review

94 Scopus citations

Abstract

The cooling and heating performances of R410A and R32 multi-heat pumps with a sub-cooler vapor injection (SCVI) were measured and compared with variations in the outdoor temperature, compressor speed, and injection ratio. Optimum injection ratios were determined to obtain maximum cooling and heating performances at a given operating condition. In the cooling mode with the optimum injection ratios, the R410A and R32 multi-heat pumps with vapor injection showed 2.1%-6.3% higher cooling capacity than those without vapor injection. In the heating mode, the R410A and R32 multi-heat pumps with vapor injection showed 7.5%-13.9% higher heating capacity than those without vapor injection, while showing 2.6%-7.0% and 1.1%-4.7% higher COPs, respectively. In addition, the SCVI cycle was more effective for improving the cooling and heating performances under extremely hot and cold weather conditions, respectively.

Original languageEnglish
Pages (from-to)179-187
Number of pages9
JournalEnergy
Volume112
DOIs
StatePublished - 1 Oct 2016

Keywords

  • Injection ratio
  • Multi-heat pump
  • R32
  • R410A
  • Vapor injection

Fingerprint

Dive into the research topics of 'Performance comparison between R410A and R32 multi-heat pumps with a sub-cooler vapor injection in the heating and cooling modes'. Together they form a unique fingerprint.

Cite this