N2 - The paper discusses topology optimization for reduction of fault current level. The problem of excessive fault current level for heavily looped power systems needs to be dealt with in the system long-term planning stage by the change of circuit breakers with higher short-circuit capacity. In the operation planning stage, however, alternative measures should be devised to reduce fault current level for critical locations. In this paper, the countermeasures of interest are bus splitting and line opening which modify power network topology. When the selected measures are applied, the magnitudes of Thevenin impedances at the critical locations would be increased and hence the fault current levels might get lower to the acceptable level. In this paper, a Tabu search on the solution space with binary variables was adopted as the solution technique to find adequate topology changing schemes to satisfying the fault level security criteria.
AB - The paper discusses topology optimization for reduction of fault current level. The problem of excessive fault current level for heavily looped power systems needs to be dealt with in the system long-term planning stage by the change of circuit breakers with higher short-circuit capacity. In the operation planning stage, however, alternative measures should be devised to reduce fault current level for critical locations. In this paper, the countermeasures of interest are bus splitting and line opening which modify power network topology. When the selected measures are applied, the magnitudes of Thevenin impedances at the critical locations would be increased and hence the fault current levels might get lower to the acceptable level. In this paper, a Tabu search on the solution space with binary variables was adopted as the solution technique to find adequate topology changing schemes to satisfying the fault level security criteria.
KW - fault level security
KW - power systems
KW - Tabu search
KW - topology modification
UR - https://www.scopus.com/pages/publications/84877807121
U2 - 10.1109/SCIS-ISIS.2012.6505386
DO - 10.1109/SCIS-ISIS.2012.6505386
M3 - Conference contribution
AN - SCOPUS:84877807121
SN - 9781467327428
T3 - 6th International Conference on Soft Computing and Intelligent Systems, and 13th International Symposium on Advanced Intelligence Systems, SCIS/ISIS 2012
SP - 2029
EP - 2032
BT - 6th International Conference on Soft Computing and Intelligent Systems, and 13th International Symposium on Advanced Intelligence Systems, SCIS/ISIS 2012
T2 - 2012 Joint 6th International Conference on Soft Computing and Intelligent Systems, SCIS 2012 and 13th International Symposium on Advanced Intelligence Systems, ISIS 2012
Y2 - 20 November 2012 through 24 November 2012
ER -